Designed for extended maintenance-free operation, Pure Lead batteries deliver consistent performance across wide temperature ranges and proven reliability for critical standby applications.
The PL-121840FT is part of our Pure Lead range. This 12.0V and 184.0Ah battery provides a space efficient design and simplified installation. Features include AGM Technology, Front Terminal, Long Shelf Life, Power Volume Ratio, SLA ABS Case, SLA Maintenance Free, and Thick Plate 10-12yr Design Life. These batteries are commonly used in Edge Data Center, Emergency Lighting, Telecomm, UPS, and Utility requiring long service life and high-rate discharge capability. Backed by decades of expertise, Power-Sonic batteries are subject to stringent quality controls through each step of the manufacturing process to ensure compliance, performance consistency, and reliability.
Cycle Applications: Apply constant voltage charge at 2.35VPC – 2.45VPC (14.1 to 14.7 volts for 12V Monobloc) at 20°C. The initial charging current should be set at less than C/5 Amps. Switch to float charge when the current falls to a 3% capacity rate to avoid overcharging. Stand-By or "Float" Service: Apply constant voltage charge of 2.25VPC – 2.30VPC (13.5 to 13.8 volts for 12V Monobloc) at 20°C. When held at this voltage, the battery will seek its own current level and maintain itself in a fully charged condition. Temperature Compensation: Charging voltage for both cyclic and stand-by applications should be regulated in relation to ambient temperature. As temperature rises, charging voltage should be reduced to prevent overcharge and increased as the temperature falls to avoid undercharge. For further charging information, including temperature compensation factors, see the Power-Sonic Technical Manual.