Storage and Maintenance

Please click on any of the below tab(s) to expand FAQs

  • We have your batteries in storage, when should they be re-boosted?
    Our batteries have a low self-discharge rate which permits storage of a fully charged battery up to a year. However, it is important that a battery be charged within six months after receipt to account for the storage from the date of manufacture to the date of purchase. Otherwise, permanent loss of capacity might occur as a result of sulfation. The rate of self discharge will vary in accordance with the ambient temperature, the higher the temperature the higher the rate of self discharge.

    More in-depth information is contained in our Technical manual on pages 10 and 11. To access our Technical Manual please go to the Literature - SLA Batteries section of our website
  • What are the acceptable storage temperatures for your sealed lead acid batteries?
    Detailed information can be found in our Technical Manual on page 10. To access our Technical Manual please go to the Literature - SLA Batteries section of our website.